Deye battery settings: Shutdown, Low Batt and Restart

On the battery setup page of a Deye hybrid inverter, three numbers decide when the battery stops, when the inverter warns you and when it starts again. Most night-time surprises come from these three.

By the Deye Monitor team · 9 November 2026 · 3 min read

In short

  • Shutdown is where the battery stops supplying the loads; Low Batt is a warning a little above it.
  • Restart is where the battery may supply again after a shutdown, and it must sit clearly higher.
  • On a lithium battery with a BMS link, set them in percent and check the result on a few real nights.

With a lithium battery linked to its BMS, the Deye uses percentages from the battery. Without that link it falls back on voltage, which is far less precise on LiFePO4. The three thresholds below work the same way in both cases.

Shutdown

When the battery reaches this level, the inverter stops drawing from it. If the grid is there, the house switches to grid. Off grid, the backup output goes dark. Setting it too low eats into the reserve the BMS keeps for its own protection.

Low Batt

A warning level a few percent above Shutdown. The inverter flags it and, on some setups, starts a generator or grid charge. It gives you time to react before the cut.

Restart

After a shutdown, the battery supplies the loads again only once it climbs back to this level. If Restart sits too close to Shutdown, the system can switch on and off several times at dawn as the first sun lifts the battery by a few percent.

Choosing values

A common starting point on lithium is around 10 to 20 percent for Shutdown, five more for Low Batt and 30 to 40 percent for Restart. Follow your battery maker first. If you want a reserve for power cuts, raise Shutdown rather than relying on the BMS to stop the pack.

Check on real nights

Deye Monitor reads the inverter on its RS485 Modbus port, next to the logger. It records battery level, work mode and alarms minute by minute, so you see at what time the battery reached Shutdown and whether it cycled at dawn. On the small screen, your home Wi-Fi and in the free Cloud.

Common questions

Why does my Deye cut the house at night with sun the next day?

The battery reached Shutdown and you have no grid, or the grid is not set to take over. Raise Shutdown or check the grid settings.

Should I use percent or voltage?

Percent, if the battery talks to the inverter through its BMS link. Voltage is a fallback for batteries without it.

Can Deye Monitor change these settings?

No. It only reads. Settings stay on the inverter.

Deye Monitor box with colour screen showing live data from a Deye hybrid inverterRJ45 RS485 socket and USB-C power input of Deye Monitor
The Deye Monitor box, real photos. Size, ports and specifications →
Hands-on

See it on your own system

Your Deye inverter, live at home and anywhere in the world

Order Deye Monitor today. Prepared and tested for your Deye model, dispatched within 3 working days.

Plug & play: working in about a minute

Order for €59Ships within 3 working days · free cancellation until dispatch